Standard Test Method for Measuring Relative Movement Capabilities of Through-Penetration Firestop Systems
Importancia y uso:
5.1 This test method is intended to standardize the cyclic movement of a through-penetration firestop system prior to a fire resistance test. If the amplitude of movement in a design application can be predicted, then the numerical values of allowable movement can be used as one data point in helping to establish suitability of the through-penetration firestop system for the given application.
Note 4: The fire resistance rating of a through-penetration firestop system is established in accordance with a relevant fire test, as acceptable to the Authority Having Jurisdiction. Examples of such tests include Test Method E814, CAN/ULC-S115, UL 1479, and ISO 10295-1.
5.2 This test method will assist users, producers, building officials, code authorities, and others in understanding relative movement capabilities of representative test specimens of through-penetration firestop systems under standardized test conditions.
5.3 This test method is not intended to predict the absolute movement capabilities of all likely permutations of through-penetration firestop systems under all likely types of real-life movement.
5.4 This test method does not provide information on:
5.4.1 Durability of the through-penetration firestop system under actual service conditions, including the effects of cycled temperature on the through-penetration firestop system;
5.4.2 Rotational shear capabilities of the test specimen;
5.4.3 Any other attributes of the test specimen, such as wear resistance, chemical resistance, air infiltration, water-tightness, and so forth; and
5.4.4 Compatibility of through-penetration firestop system components and the penetrating items.
5.5 This test method is only to be used as one element in the selection of a through-penetration firestop system for a particular application.
5.6 This is not a fire test standard. To determine the effect of cyclic movement on the fire resistance rating of a though-penetration firestop system, conduct a fire test in accordance with a fire resistance test method acceptable to the Authority Having Jurisdiction subsequent to this movement test.
Subcomité:
E06.21
Referida por:
E3157-23
Volúmen:
04.12
Número ICS:
13.220.50 (Fire-resistance of building materials and elements), 23.040.99 (Other pipeline components), 91.060.10 (Walls. Partitions. Facades)
Palabras clave:
cyclic; displacement; fire; firestop; movement; penetration; seismic; test;
$ 1,228
Norma
E3037
Versión
20
Estatus
Active
Clasificación
Test Method
Fecha aprobación
2020-07-01