Standard Practice for Estimation of Heat Savings by Adding Thermal Insulation to Bare Valves and Flanges


Importancia y uso:

5.1 Manufacturers of thermal insulation for valves typically express the performance of their products in charts and tables showing heat loss per valve. These data are presented for both bare and insulated valves of different pipe sizes, ANSI classes, insulation types, insulation thicknesses, and service temperatures. Additional information on effects of wind velocity, jacket emittance, bare valve emittance, and ambient conditions are also required to properly select an insulation system. Due to the infinite combination of pipe sizes, ANSI classes, insulation types and thicknesses, service temperatures, insulation cover geometries, surface emittance values, and ambient conditions, it is not possible to publish data for each possible case.

5.2 Users of thermal insulation for piping systems faced with the problem of designing large systems of insulated piping, encounter substantial engineering costs to obtain the required thermal information. This cost can be substantially reduced by both the use of accurate engineering data tables, or by the use of available computer analysis tools, or both.

5.3 The use of this practice by the manufacturer, contractor, and users of thermal insulation for valves and flanges will provide standardized engineering data of sufficient accuracy and consistency for predicting the savings in heating energy use by insulating bare valves and flanges.

5.4 Computers are now readily available to most producers and consumers of thermal insulation to permit use of this practice.

5.5 The computer program in Practice C680 has been developed to calculate the heat loss per unit length, or per unit surface area, of both bare and insulated pipe. With values for bare valve or flange surface areas, heat loss can be estimated. By estimating the outer insulation surface area from an insulation manufacturer's or contractor's drawings, the heat loss from the insulation surface can likewise be calculated by taking the product of heat loss per unit area (from programs conforming to Practice C680) and the valve or flange insulation surface area. The area of the uninsulated surfaces also will need to be considered.

5.6 The use of this practice requires that the valve or flange insulation system meets either Specification C1695 for removeable/reuseable or the Adjunct to Practice C4503 for insulation fabricated from rigid board and pipe insulation.

Subcomité:

C16.30

Referida por:

C1695-22

Volúmen:

04.06

Número ICS:

23.040.60 (Flanges, couplings and joints)

Palabras clave:

calculated energy savings; flanges; heat loss; heat loss from pipes; pipe systems ; valves;

$ 1,084

Agregar al carrito

Norma
C1129

Versión
17

Estatus
Active

Clasificación
Practice

Fecha aprobación
2017-03-01