Standard Guide for Determining Blown Density of Pneumatically Applied Loose-Fill Mineral Fiber Thermal Insulation


Importancia y uso:

4.1 Blown density is used to develop loose-fill coverage charts. Data for blown density vs thickness is used in the development of a variable blown density presentation for loose-fill insulation.

4.2 Thermal resistance (and conductivity) of loose-fill mineral fiber insulation depends on density and thickness. The resulting blown density data is useful in developing an expression for apparent thermal conductivity as a function of density. This will in turn aid the manufacturer in developing coverage information for packages of loose-fill insulation.

4.3 The blown density obtained in this method is for the thickness of the test only. The relationship of blown density with thickness can be determined by repeating the procedures outlined here using different thicknesses.

4.4 These procedures are not the same as the test method described in Test Method C1374. Depending on the test conditions utilized, the blown density may, or may not, represent the installed density values obtained by using Test Method C1374.

4.5 This guide can be used to develop appropriate blowing machine settings to achieve a target blown density at a predetermined thickness.

Subcomité:

C16.32

Referida por:

C0764-25, C1630-24

Volúmen:

04.06

Número ICS:

91.100.60 (Thermal and sound insulating materials)

Palabras clave:

blown density; loose-fill; mineral fiber; thermal insulation;

$ 1,187

Agregar al carrito

Norma
C1574

Versión
25

Estatus
Active

Clasificación
Guide

Fecha aprobación
2025-05-01