Standard Test Methods for Measuring Resistance of Electrical Connections (Static Contacts)
Importancia y uso:
5.1 As stated in Terminology B542, contact resistance is comprised of a constriction resistance and a film resistance. When present, the latter of these is usually much greater in value and dominates the contact resistance. For a given contact spot, when the film resistance is zero or negligible the contact resistance for that spot is nearly the same as the constriction resistance and therefore, as a practical matter, has a minimum value which represents a clean metal-to-metal contact spot. As real contact surfaces exhibit varying degrees of roughness, real contacts are necessarily composed of many contact spots which are electrically parallel. In practical cases the clean metal-to-metal contact spots will carry most of the current and the total contact resistance is primarily dependent on the size and number of metallic contact spots present (see Note 1). In addition, acceptably low values of contact resistance are often obtained with true areas of contact being significantly less than the apparent contact area. This is the result of having a large number of small contact spots spread out over a relatively large apparent contact area.
Note 1: The term metallic contact as used here is intended to include the so called quasi-metallic contact spots as well. The latter case was discussed in Electric Contacts by Holm. 3
5.2 The practical evaluation and comparison of electrical connections depend in large part on their contact resistance characteristics. On the one hand, the absolute value of contact resistance is greatly dependent on the size and distribution of the metallic conducting spots within the apparent area of load-bearing contact. On the other hand, a comparison of the initial resistance to the resistance after aging indicates how stable the system is in maintaining the initial contact area. Both of these characteristics should be considered when evaluating contact systems. The criteria employed in evaluating contact resistance and stability are not a part of these test methods as they depend on specific applications and therefore, will not be quantitatively stated. However, an estimate of contact resistance3 resulting from good metallic contact can be made for a given physical situation and used as a comparison to actual measurements to determine how effective the system is in establishing stable metallic contact. Resistances measured by these methods before, during and after simulated life tests are used as a means of determining the stability of contacts within a device.
Subcomité:
B02.05
Referida por:
B1004-16R22, B0896-10R20, B0942-21, B0854-98R22, B0885-09R20, B0794-97R20
Volúmen:
02.04
Número ICS:
29.120.20 (Connecting devices)
Palabras clave:
connection resistance; connectors; contact resistance; contacts; electrical resistance; junction resistance; low level contact resistance; separable connections;
$ 1,086
Norma
B539
Versión
20
Estatus
Active
Clasificación
Test Method
Fecha aprobación
2020-04-01