Standard Test Method for Determining the Protective Performance of a Shield Attached on Live Line Tools or on Racking Rods for Electric Arc Hazards


Importancia y uso:

5.1 This test method is intended for determining the heat attenuation factor (HAF) of a shield material and the effective heat attenuation factor (EHAF) at the location of the worker. This can be obtained by measuring the reduction of the arc incident energy levels caused by a shield attached on a live line tool (hot stick) or on a racking rod and designed for protection for workers exposed to electric arcs. The shield mechanical strength (SMS) can be obtained from visual observations of the high speed video recordings of each shot during HAF tests.

5.1.1 Because of the variability of the arc exposure, different heat transmission values and pressure may result for individual sensors. The results of each sensor are evaluated in accordance with Section 12.

5.2 This test method maintains the shield and the heat sensors in a static, vertical position and does not involve movement except that resulting from the exposure.

5.3 This test method specifies a standard set of exposure conditions. Different exposure conditions may produce different results.

Note 1: In addition to the standard set of exposure conditions, other conditions representative of the expected hazard may be used and shall be reported should this data be cited.

Subcomité:

F18.35

Volúmen:

10.03

Número ICS:

13.260 (Protection against electric shock. Live working)

Palabras clave:

cone of protection; effective heat attenuation factor (EHAF); heat attenuation factor (HAF); protective performance of a shield; shield mechanical strength (SMS) value;

$ 1,121

Agregar al carrito

Norma
F2522

Versión
12(2022)

Estatus
Active

Clasificación
Test Method

Fecha aprobación
2022-11-01