Standard Test Method for High-Voltage, Low-Current, Dry Arc Resistance of Solid Electrical Insulation


Importancia y uso:

4.1 The high-voltage, low-current type of arc resistance test is intended to simulate only approximately such service
conditions as exist in alternating current circuits operating at high voltage, but at currents limited to units and tens of milliamperes.

4.2 In order to distinguish more easily among materials that have low arc resistance, the early stages of this test method are mild, and the later stages are successively more severe. The arc occurs intermittently between two electrodes resting on the surface of the specimen, in normal or inverted orientation. The severity is increased in the early stages by successively decreasing to zero the interval between flashes of uniform duration, and in later stages by increasing the current.

4.3 Four general types of failure have been observed:

4.3.1 Many inorganic dielectrics become incandescent, whereupon they are capable of conducting the current. Upon cooling, however, they return to their earlier insulating condition.

4.3.2 Some organic compounds burst into flame without the formation of a visible conducting path in the substance.

4.3.3 Others are seen to fail by “tracking,” that is, a thin wiry line is formed between the electrodes.

4.3.4 The fourth type occurs by carbonization of the surface until sufficient carbon is present to carry the current.

4.4 Materials often fail within the first few seconds after a change in the severity stage. When comparing the arc resistance of materials, much more weight shall be given to a few seconds that overlap two stages than to the same elapsed time within a stage. Thus, there is a much greater difference in arc resistance between 178 and 182 s than between 174 and 178 s.

Note 4: Some investigators have reported attempts to characterize the remaining insulating value of the damaged area after failure by allowing the specimen to cool to room temperature, without disturbance of the original position of the electrodes, and then either (1) measuring the insulation resistance between the electrodes or (2) determining the percentage of breakdown voltage remaining relative to that obtained on an undamaged area of the specimen. A recommended circuit arrangement and test procedure for carrying out the second of these two means of characterizing the remaining insulating value of the damaged area is described in Appendix X1. Still another, and obvious, method of reevaluating the damaged area after failure is to repeat the arc resistance test after the specimen has cooled, with the electrodes undisturbed from their original positions. However, keep in mind that none of these methods will be universally applicable because of the severe physical damage to the test area in many instances.

Subcomité:

D09.12

Referida por:

D0710-19, D0705-99R20, D1201-13R22E01, D7745-19, D0709-17, G0021-15R21E01, D4000-23, D1304-99R20E01, D4101-24, D0704-99R20, D5948-05R20, D1755-21, D0229-19E01, D1039-16R22, D0619-21

Volúmen:

10.01

Número ICS:

29.035.01 (Insulating materials in general)

Palabras clave:

arc resistance; dry arc resistance; high voltage; low current; stainless steel electrodes; tungsten rod electrodes;

$ 1,194

Agregar al carrito

Norma
D495

Versión
22

Estatus
Active

Clasificación
Test Method

Fecha aprobación
2022-01-15