Standard Test Method for Low-Level Dissolved Oxygen in Water
Importancia y uso:
5.1 Dissolved oxygen is detrimental in certain boiler and steam cycles because it may accelerate corrosion. Concentrations above 10 μg/L are unacceptable in many high-pressure boiler systems. The efficiency of dissolved oxygen removal from boiler feedwater by chemical or mechanical means, or both, is determined by measuring the concentration before and after the process. The measurement is also made to check for air leakage into the boiler system.
5.2 The oxygen treatment method for boiler corrosion reduction requires injection of oxygen into the boiler feedwater. The resulting oxygen level is monitored for control purposes.
Subcomité:
D19.03
Volúmen:
11.01
Número ICS:
13.060.50 (Examination of water for chemical substances)
Palabras clave:
ampoules; boiler; boiler feedwater; colorimetric analysis; dissolved oxygen; oxygen; oxygen sensitive indicator; steam; steam condensate; petroleum refining; power generation;