Standard Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using VDE Electrodes
Importancia y uso:
3.1 The dielectric breakdown voltage of an insulating liquid is of importance as a measure of the liquid's ability to withstand electric stress without failure. The dielectric breakdown voltage serves to indicate the presence of contaminating agents such as water, dirt, cellulosic fibers, or conducting particles in the liquid, one or more of which may be present in significant concentrations when low breakdown voltages are obtained. However, a high dielectric breakdown voltage does not necessarily indicate the absence of all contaminants; it may merely indicate that the concentrations of contaminants that are present in the liquid between the electrodes are not large enough to deleteriously affect the average breakdown voltage of the liquid when tested by this test method (see Appendix X1.)
3.2 This test method is used in laboratory or field tests. For field breakdown results to be comparable to laboratory results, all criteria including room temperature (20 to 30 °C) must be met.
Subcomité:
D27.05
Referida por:
D8180-23, D5222-23, D2413-16R22, D4652-20, D6871-17, D3487-24, D8240-22E01, D3394-16R22, D0877_D0877M-19E01, D2225-20, D0117-22, D0877_D0877M-19E01
Volúmen:
10.03
Número ICS:
29.040.10 (Insulating oils)
Palabras clave:
breakdown voltage; dielectric strength; insulating liquids; insulating oils; test cell; VDE electrodes;
$ 1,090
Norma
D1816
Versión
12(2019)
Estatus
Active
Clasificación
Test Method
Fecha aprobación
2019-10-01